国产亚洲高清精品成人-国产白浆成人免费试看-熟妇人妻无码激情视频-久久免费少妇高潮久久精品99

當(dāng)前位置:首頁(yè)-新聞中心新聞中心

濟(jì)南鐵皮風(fēng)管加工:風(fēng)管下加下噴淋頭安裝規(guī)范

發(fā)布人:http://yongyi123.com   發(fā)布時(shí)間:2024-08-28 09:49:33

  風(fēng)管寬度超過(guò)1.2米時(shí),應(yīng)當(dāng)在管道下方安裝噴淋,采用下噴的形式,噴頭應(yīng)當(dāng)設(shè)置在管道的下方,而不應(yīng)與管道齊平或者設(shè)置在管道上方或側(cè)方。噴淋頭間距不能小于15公分,注意放水時(shí)不能打開(kāi)通風(fēng)。采用早期抑制快速響應(yīng)噴頭和特殊應(yīng)用噴頭的場(chǎng)所,當(dāng)障礙物寬度大于0.6m時(shí),其下方應(yīng)增設(shè)噴頭。

  When the width of the air duct exceeds 1.2 meters, a sprinkler should be installed below the duct, using a downward spray form. The sprinkler should be placed below the duct, not flush with the duct or above or on the side of the duct. The distance between sprinkler heads should not be less than 15 centimeters, and attention should be paid to not opening ventilation when draining water. In places where early suppression rapid response nozzles and special application nozzles are used, nozzles should be added below obstacles with a width greater than 0.6m.

20230923445793.jpg

  消防噴淋系統(tǒng)噴頭安裝基本要求

  Basic requirements for installation of fire sprinkler system nozzles

  1、直立型噴頭安裝距樓板頂部距離為規(guī)范要求為75mm-150mm。

  1. The installation distance of the upright nozzle from the top of the floor slab is required by the specifications to be 75mm-150mm.

  2、有吊頂?shù)南麓剐蛧婎^安裝噴頭根部應(yīng)與吊頂平齊,為避免定位不準(zhǔn),可在吊頂龍骨標(biāo)高確定后再安裝下噴支管;下噴頭與三通之間的短管長(zhǎng)度不宜超過(guò)150mm。

  2. The installation of hanging nozzles with suspended ceilings should be flush with the base of the nozzle. To avoid inaccurate positioning, the lower spray pipe can be installed after the elevation of the ceiling keel is determined; The length of the short pipe between the nozzle and the tee should not exceed 150mm.

  3、邊墻型噴頭安裝離墻距離為50-100mm。

  3. The installation distance of the side wall type nozzle from the wall is 50-100mm.

  4、無(wú)吊頂時(shí)設(shè)置上噴頭;有吊頂時(shí)設(shè)置下噴頭,當(dāng)?shù)蹴斏戏綈烅數(shù)膬艨崭叨瘸^(guò)800mm,且其內(nèi)部有可燃物時(shí),要求設(shè)置上噴頭;噴頭在系統(tǒng)沖洗試壓合格后安裝;當(dāng)噴淋支管高度大于1000mm時(shí),應(yīng)設(shè)橫向加強(qiáng)支架;當(dāng)不確定裝修方案是否有吊頂時(shí)可預(yù)留三通口,絲堵封堵。

  4. Install upper nozzles when there is no ceiling; When there is a suspended ceiling, a lower nozzle should be installed. When the clearance height above the suspended ceiling exceeds 800mm and there are combustibles inside, an upper nozzle should be installed; The nozzle shall be installed after the system flushing and pressure test is qualified; When the height of the spray branch pipe is greater than 1000mm, a transverse reinforcement bracket should be installed; When it is uncertain whether the decoration plan has a suspended ceiling, a three-way port can be reserved and sealed with a screw plug.

  5、噴淋管道末端應(yīng)采用梯形防晃支架;末端支架與噴頭之間的距離為400mm

  5. The end of the sprinkler pipe should be equipped with a trapezoidal anti sway bracket; The distance between the end bracket and the nozzle is 400mm

  6、當(dāng)梁、通風(fēng)管道、排管、橋架寬度大于1.2m時(shí),增設(shè)的噴頭應(yīng)安裝在其腹面以下部位;風(fēng)管下噴頭吊架應(yīng)采取管道延長(zhǎng)風(fēng)管另外一端邊緣,并在延伸管道末端設(shè)置吊架。

  6. When the width of beams, ventilation ducts, ducts, and cable trays is greater than 1.2m, additional nozzles should be installed below their belly surface; The nozzle hanger under the air duct should be extended to the edge of the other end of the air duct, and a hanger should be installed at the end of the extended pipe.

  7、噴淋管道安裝應(yīng)主管在下;噴淋管支管在主管上方,朝主管方向形成坡度,便于系統(tǒng)維護(hù)泄水。

  7. The installation of sprinkler pipes should be supervised by the supervisor; The spray pipe branch is located above the main pipe, forming a slope towards the main pipe direction for easy maintenance and drainage of the system.

本文由濟(jì)南鑫淼通風(fēng)設(shè)備有限公司 友情奉獻(xiàn).更多有關(guān)的知識(shí)請(qǐng)點(diǎn)擊:http://yongyi123.com/news/真誠(chéng)的態(tài)度.為您提供為的服務(wù).更多有關(guān)的知識(shí)我們將會(huì)陸續(xù)向大家奉獻(xiàn).敬請(qǐng)期待.

This article is a friendly contribution from Jinan Xinmiao Ventilation Equipment Co., Ltd. For more related knowledge, please click: http://yongyi123.com/news/ Sincere attitude. We provide you with comprehensive services. We will gradually contribute more relevant knowledge to everyone. Please stay tuned

上一篇:濟(jì)南風(fēng)管加工廠:通風(fēng)管道的清洗和維護(hù)周期一般是多久呢?
下一篇:濟(jì)南通風(fēng)管道:通風(fēng)管道技術(shù)規(guī)程——風(fēng)管安裝

網(wǎng)站首頁(yè) 關(guān)于我們 產(chǎn)品展示 新聞中心 工程案例 在線留言 聯(lián)系我們

在线一区二区在线视频| 国产盗摄国产盗摄视频在线| 亚洲午夜精品福利网站| 国产精品日本孕妇网站| 亚洲国产一区二区精品在线| 国产盗摄国产盗摄视频在线| 综合亚洲欧美一区二区| 色哟哟色播一区二区三区| 五月开心婷婷开心五月活动推荐| 福利在线视频欧美激情| 久久精品久久久观看水蜜桃| 羞辱老头奶水丰满人妻| 高清国产精品日韩成人av| 色狠狠一区二区三区中文 | 国产成人免费97在线| 91高清直播在线观看| 欧美日韩国产精品久久一区二区| 国产av天天爽天天干| 亚洲午夜精品福利网站| 国产午夜免费啪视频观看视| 一区二区三区日韩精品| 亚洲精品一区二区小说| 丝袜美腿在线观看中文字幕 | 97在线观看视频免费| 人妻连裤丝袜中文字幕| 精品视频美女一区二区三区| 亚洲欧美综合一区自拍| 亚洲精品一区二区小说| 日本到在线高清视频观看| 亚洲影视精品一区二区三区| 在线一区二区在线视频| 奇米影视狠狠精品一区| 欧美色欧美亚洲一区二区三区| 亚洲影视精品一区二区三区 | 八上语文富贵不能淫课文| 麻豆欧美精品国产综合久久| 久久精品久久久观看水蜜桃| 日韩欧美视频午夜福利视频| 亚洲国产成人久久精品美女av| 国产成人免费97在线| 91码精品一区二区三区|